Call: 937-667-8484
Email: sales@captorcorp.com
EMI & EMC Solutions > HEMP Filters Control/Signal Line > Control/Signal Line HEMP Filters Standard Performance > Item # A-10358  
Download PDF Download PDF     Printable Page     Email Email This Page     Save To Favorites Save To Favorites

Item # A-10358, 5 Ampere (A) Current Control/Signal Line HEMP Filter Standard Performance



  • Voltage Rating : 48 VDC or 120 VAC @ 0-60 Hz
  • Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
  • Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
  • Insulation Resistance : Per MIL-PRF-15733, paragraph 4.6.7 with Hemp Protection Module removed.
  • Dielectric Withstanding Voltage : Per MIL-PRF-15733, paragraph 4.6.5 with Hemp Protection Module removed.
  • Standard Insertion Loss : Per MIL-STD-220, 20 dB @ 10 kHz, 80 dB @ 10 MHz to 10 GHz
  • Terminal Strength : Per MIL-PRF-15733, paragraph 4.6.11
  • Voltage Discharge : Discharge to less than 30 Volts within 2 seconds after removal of power
  • Terminals : 1/4" Quick Connect Tab
  • Operating Temperature : -55 ºC to +71 ºC
  • Storage Temperature : -55 ºC to +105 ºC
  • Chassis & Terminal Finish : Electro Tin-Lead
  • Chassis Material : 20 GA. Cold Rolled Steel





Specifications  · Major Dimensions  · Chassis Material  · Features  · Note

Specifications

Brands

Captor

Voltage Rating (DC)

48 V @ 0 to 60 Hz

Frequency

0 to 60 Hz

Current

5 A

Insertion Loss Curve

High-Altitude Electromagnetic Pulse (HEMP) Residual

< 0.1 A

Visual/Mechanical

Per MIL-PRF-15733, Paragraph 4.6.1

Capacitance

Per MIL-STD-202, Method 305 @ 1 kHz

Insulation Resistance

Per MIL-PRF-15733, Paragraph 4.6.7 with HEMP Protection Module Removed

Dielectric Withstanding Voltage

Per MIL-PRF-15733, Paragraph 4.6.5 with HEMP Protection Module Removed

Standard Insertion Loss

Per MIL-STD-220, 20 dB @ 10 kHz, 80 dB @ 10 MHz to 10 GHz

Terminal Strength

Per MIL-PRF-15733, Paragraph 4.6.11

Voltage Discharge

Discharge to less than 30 Volts within 2 seconds after removal of power

Quick Connect Tab Terminals

1/4 in

Operating Temperature

-55 to +71 ºC

Storage Temperature

-55 to +105 ºC

Chassis & Terminal Finish

Electro Tin-Lead

Minimum Insertion Loss

20 dB @ 10 kHz
40 dB @ 100 kHz

60 dB @ 1 MHz

80 dB @ 10 MHz to 10 GHz

Compliance

MIL-STD-188-125-1
MIL-STD-188-125-2


Major Dimensions

Major Dimension A

8.40 in

Major Dimension B

6.00 in

Major Dimension C

2.00 in

Major Dimension D

3.00 in


Chassis Material

Chassis Material

Cold Rolled Steel (CRS)

Chassis Material Thickness

20 gauge


Features
  • Inductive Input.
  • Individually Filtered Lines.
  • Standard Performance and High Performance Insertion Loss Versions.
  • Captor can Supply Enclosures Holding Multiple Filters.
  • Field Replaceable HEMP Protection Module.
  • Custom Options Available.




Note
For compliance to E2 (intermediate pulse) add an "A" to the end of the part number (A-10356A).



 MORE IMAGES 

·  Curve 1, Minimum Insertion Loss


 DOWNLOADS 

Control-Signal-Line-HEMP-Filters
(PDF, 342KB)


Site created by Thomas Web Solutions and powered by Navigator PlatformPrivacy  |  Sitemap  |  Catalog Index
Copyright © 2017 Captor Corporation, All Rights Reserved