Item # A-10369, 2 Ampere (A) Control/Signal Line HEMP Filter High Performance

List Price QUOTE


  • Voltage Rating : 48 VDC or 120 VAC @ 0-60 Hz
  • Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
  • Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
  • Insulation Resistance : Per MIL-PRF-15733, paragraph 4.6.7 with HEMP Protection Module removed.
  • Dielectric Withstanding Voltage : Per MIL-PRF-15733, paragraph 4.6.5 with HEMP Protection Module removed.
  • High Performance Insertion Loss: Per MIL-STD-220, 100 dB @ 14 kHz - 10 GHz
  • Terminal Strength : Per MIL-PRF-15733, paragraph 4.6.11
  • Voltage Discharge : Discharge to less than 30 Volts within 2 seconds after removal of power
  • Terminals : 1/4" Quick Connect Tab
  • Operating Temperature : -55 ºC to +71 ºC
  • Storage Temperature : -55 ºC to +105 ºC
  • Chassis & Terminal Finish : Electro Tin-Lead
  • Chassis Material : 20 GA. Cold Rolled Steel





Specifications  · Major Dimensions  · Chassis Material  · Features  · Note

Specifications

Brands

Captor

Voltage Rating (AC)

120 V

Frequency

0 to 60 Hz

Current

2 A

Insertion Loss Curve

High-Altitude Electromagnetic Pulse (HEMP) Residual

< 1 A

Visual/Mechanical

Per MIL-PRF-15733, Paragraph 4.6.1

Capacitance

Per MIL-STD-202, Method 305 @ 1 kHz

Insulation Resistance

Per MIL-PRF-15733, Paragraph 4.6.7 with HEMP Protection Module Removed

Dielectric Withstanding Voltage

Per MIL-PRF-15733, Paragraph 4.6.5 with HEMP Protection Module Removed

High Performance Insertion Loss

Per MIL-STD-220, 100 dB @ 14 kHz to 10 GHz

Terminal Strength

Per MIL-PRF-15733, Paragraph 4.6.11

Voltage Discharge

Discharge to less than 30 Volts within 2 seconds after removal of power

Quick Connect Tab Terminals

1/4 in

Operating Temperature

-55 to +71 ºC

Storage Temperature

-55 to +105 ºC

Chassis & Terminal Finish

Electro Tin-Lead

Minimum Insertion Loss

100 dB @ 14 kHz to 10 GHz

Compliance

MIL-STD-188-125-1
MIL-STD-188-125-2


Major Dimensions

Major Dimension A

7.40 in

Major Dimension B

5.00 in

Major Dimension C

1.25 in

Major Dimension D

2.50 in


Chassis Material

Chassis Material

Cold Rolled Steel (CRS)

Chassis Material Thickness

20 gauge


Features
  • Inductive Input.
  • Individually Filtered Lines.
  • Standard Performance and High Performance Insertion Loss Versions.
  • Captor can Supply Enclosures Holding Multiple Filters.
  • Field Replaceable HEMP Protection Module.
  • Custom Options Available.




Note
For compliance to E2 (intermediate pulse) add an "A" to the end of the part number (A-10356A)
For 120 VAC units only, compliance to E2 increases overall dimension "A" by 2.5 inches.