Tempest Filter # A-10303, 10 Ampere (A) Current High Performance TEMPEST Filter

List Price QUOTE


  • Voltage Rating : 120/250 VAC @ 0-60 Hz
  • Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
  • Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
  • Insulation Resistance : 1500 MΩ minimum per MIL-STD-202, Method 302
  • Dielectric Withstanding Voltage : 800 VDC line-to-line & line-to-chassis per MIL-STD-202, Method 301
  • Insertion Loss : Per MIL-STD-220,100 dB @ 14 kHz to 10 GHz
  • Voltage Drop : Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
  • Terminal Strength : Per MIL-PRF-15733 Paragraph 4.6.11
  • Voltage Discharge : Discharge to less than 30 Volts within 30 s after removal of power
  • Threaded Terminals : 8-32 UNC-2A
  • Threaded Inserts : 8-32 UNC-2B
  • Operating Temperature : -55 ºC to+71 ºC
  • Storage Temperature : -55 ºC to +105 ºC
  • Chassis & Terminal Finish : Electro Tin-Lead
  • Chassis Material : CRS





Specifications  · Major Dimensions  · Chassis Material  · Features  · Note

Specifications

Voltage Rating (AC)

120 V @ 0 to 60 Hz
250 V @ 0 to 60 Hz

Frequency

0 to 60 Hz

Current

10 A

Insertion Loss Curve

Leakage Current

< 1.6 A

Input Connection

D38999/20WE6PN

Output Connection

8-32 Stud Assemblies

Visual/Mechanical

Per MIL-PRF-15733, Paragraph 4.6.1

Capacitance

Per MIL-STD-202, Method 305 @ 1 kHz

Insulation Resistance

1500 MΩ minimum per MIL-STD-202, Method 302

Dielectric Withstanding Voltage

800 VDC line-to-line & line-to-chassis per MIL-STD-202, Method 301

Insertion Loss

Per MIL-STD-220, 100 dB @ 14 kHz to 10 GHz

Voltage Drop

Less than 1% of Rated Voltage Per Paragraph 4.6.8 of MIL-PRF-15733

Terminal Strength

Per MIL-PRF-15733, Paragraph 4.6.11

Voltage Discharge

Discharge to Less than 30 Volts within 30 s After Removal of Power

Threaded Terminals

8-32 UNC-2A

Threaded Inserts

8-32 UNC-2B

Operating Temperature

-55 to +71 ºC

Storage Temperature

-55 to +105 ºC


Major Dimensions

Major Dimension A

7.00 in

Major Dimension B

4.50 in

Major Dimension C

3.00 in


Chassis Material

Chassis & Terminal Finish

Electro Tin-Lead

Chassis Material

Cold Rolled Steel (CRS)


Features
  • Individually Filtered Lines.
  • High Performance TEMPEST Filters.
  • Alternate Mounting Means Available.
  • Captor can Supply Enclosure Housing with Multiple Filters.
  • Custom Options Available.




Note
Specifications subject to change.



 MORE IMAGES 

·  High Performance TEMPEST Filters with High-Altitude Electromagnetic Pulse (HEMP) Protection Option - 2

·  Minimum Insertion Loss Curve, 100 dB at 14 kHz to 10 GHz


 DOWNLOADS 

High Performance TEMPEST Filters
(PDF, 298KB)