Print Back

Specifications

  • Voltage Rating: 277/480 VAC @ 60 Hz
  • Current Rating: 50 through 800 Amperes
  • Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
  • Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to installation of discharge resistor
  • Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
  • Voltage Discharge: Discharge to less than 30 Volts within 30s after removal of power
  • Operating Temperature: -40° C to +65° C
  • Storage Temperature: -55° C to +105° C
  • Insertion Loss: Measured per MIL-STD-220
Enclosure
  • Modified: NEMA 1 type enclosure
  • Cabinet Material: Stainless Steel construction
  • Filter insert case material: Cold rolled steel construction with a corrosion resistant plating
  • Epoxy paint optional
  • Shielding effectiveness measured on clean side greater than 100 dB from 14KHz or 100KHz to 10 GHz
  • Dual removable access covers
Shielded Facility Room Power Line Filters
Unit of Measure
Items Shielded Facility Room Power Line Filters
A-11030-2
2 Line 50 Ampere (A) Current Rating High Performance Shielded Facility Room Power Line Filter
Shielded Facility Room Power Line Filters
A-11030-3
3 Line 50 Ampere (A) Current Rating High Performance Shielded Facility Room Power Line Filter
Shielded Facility Room Power Line Filters
A-11030-4
4 Line 50 Ampere (A) Current Rating High Performance Shielded Facility Room Power Line Filter
Shielded Facility Room Power Line Filters
A-11031-2
2 Line 100 Ampere (A) Current Rating High Performance Shielded Facility Room Power Line Filter
Shielded Facility Room Power Line Filters
A-11031-3
3 Line 100 Ampere (A) Current Rating High Performance Shielded Facility Room Power Line Filter
Description N/A 100dB, 14KHz to 1 GHz measured per MIL-STD-220, 50ohms system 10 to 100% load current
Brands N/A Captor
Alternating Current (AC) Voltage at 60 Hertz (Hz) N/A 270 V480 V
Insulation Resistance N/A Per MIL-PRF-15733, prior to discharge resistor installation.
Dielectric Withstanding Voltage N/A 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to installation of discharge resistor
Voltage Drop N/A Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
Voltage Discharge N/A Discharge to less than 30 Volts within 30s after removal of power
Operating Temperature N/A -40 to +65 ºC
Storage Temperature N/A -55 to +105 ºC
Insertion Loss N/A Measured per MIL-STD-220
Filter Type N/A High Performance Filter
Number of Lines N/A 2 N/A 3 N/A 4 N/A 2 N/A 3
Current Rating N/A 50 A N/A 50 A N/A 50 A N/A 100 A N/A 100 A
Size A N/A 13.0 in N/A 19.0 in N/A 25.0 in N/A 15.0 in N/A 21.0 in
Size B N/A 28.0 in N/A 28.0 in N/A 28.0 in N/A 32.0 in N/A 32.0 in
Size C N/A 7.0 in
Size D N/A 18.0 in N/A 18.0 in N/A 18.0 in N/A 22.0 in N/A 22.0 in
Size E N/A 14.0 in N/A 20.0 in N/A 26.0 in N/A 16.0 in N/A 22.0 in
Estimated Weight N/A 110 lb N/A 175 lb N/A 230 lb N/A 180 lb N/A 280 lb
Enclosure N/A
  • Modified: NEMA 1 type enclosure
  • Cabinet Material: Stainless Steel construction
  • Filter insert case material: Cold rolled steel construction with a corrosion resistant plating
  • Epoxy paint optional
  • Shielding effectiveness measured on clean side greater than 100 dB from 14 KHz or 100 KHz to 10 GHz
  • Dual removable access covers
Note N/A When installed with best grounding practice, additional shielding and Isolation between input and output compartments
Specifications subject to change
Cabinet Supplied with Filter Inserts, 50 to 800 Amps 2, 3 and 4 Power Line filters Installed