CAD (0)
  • Cart is empty
  • Shielded Facility Room Power Line Filters

    Specifications

    • Voltage Rating: 277/480 VAC @ 60 Hz
    • Current Rating: 50 through 800 Amperes
    • Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
    • Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to installation of discharge resistor
    • Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
    • Voltage Discharge: Discharge to less than 30 Volts within 30s after removal of power
    • Operating Temperature: -40° C to +65° C
    • Storage Temperature: -55° C to +105° C
    • Insertion Loss: Measured per MIL-STD-220
    Enclosure
    • Modified: NEMA 1 type enclosure
    • Cabinet Material: Stainless Steel construction
    • Filter insert case material: Cold rolled steel construction with a corrosion resistant plating
    • Epoxy paint optional
    • Shielding effectiveness measured on clean side greater than 100 dB from 14KHz or 100KHz to 10 GHz
    • Dual removable access covers