CAD (0)
▾
-
HEMP Filters Power, Control, and Signal Lines
hemp-filters-power-control-and-signal-lines
-
Power Line HEMP Filters Standard Performance
- Voltage Rating: 277/480 VAC @ 60 Hz
- Current Rating: 5 through 150 amperes
- HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
- Insertion Loss: Standard performance (curve 1) per MIL-STD-220
- Leakage Current: < 10% of rated current 10 through 150 amperes, < 1 amp for 5 amp filters
- Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
- Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to surge arrestor and discharge resistor installation
- Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
- Voltage Discharge: Discharge to less than 30 Volts within 30 s after removal of power
- Operating Temperature: -40 ºC to +65 ºC
- Storage Temperature: -55 ºC to +105 ºC
-
Power Line HEMP Filters High Performance
- Voltage Rating: 277/480 VAC @ 60 Hz
- Current Rating: 5 through 150 amperes
- HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
- Insertion Loss: high performance (curve 2) per MIL-STD-220
- Leakage Current: < 10% of rated current 10 through 150 amperes, <1 amp for 5 amp filters
- Insulation Resistance: Per MIL-PRF-15733, prior to discharge resistor installation.
- Dielectric Withstanding Voltage: 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to surge arrestor and discharge resistor installation
- Voltage Drop: Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733
- Voltage Discharge: Discharge to less than 30 Volts within 30 s after removal of power
- Operating Temperature: -40 ºC to +65 ºC
- Storage Temperature: -55 ºC to +105 ºC
-
Power Line HEMP Filters Legacy
- Voltage : 0 to 480 Volts
- Current : 0 to 100 Amps
- Frequency : DC to 400 Hz
- Insertion Loss : 100 dB minimum from 14 kHz to 10 GHz
- Operating Temperature : -40 ºC to +71 ºC
- Storage Temperature : -55 ºC to +105 ºC
- Altitude : Maximum of 15,000 feet
- Humidity : 10 to 90 Percent
- Fungus : Non-nutritive materials are used
- Corrosion : Hermetically sealed steel or aluminum enclosures with tin-lead plating
-
Control/Signal Line HEMP Filters Standard Performance
- Voltage Rating : 48 VDC or 120 VAC @ 0-60 Hz
- Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
- Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
- Insulation Resistance : Per MIL-PRF-15733, paragraph 4.6.7 with Hemp Protection Module removed.
- Dielectric Withstanding Voltage : Per MIL-PRF-15733, paragraph 4.6.5 with Hemp Protection Module removed.
- Standard Insertion Loss : Per MIL-STD-220, 20 dB @ 10 kHz, 80 dB @ 10 MHz to 10 GHz
- Terminal Strength : Per MIL-PRF-15733, paragraph 4.6.11
- Voltage Discharge : Discharge to less than 30 Volts within 2 seconds after removal of power
- Terminals : 1/4" Quick Connect Tab
- Operating Temperature : -55 ºC to +71 ºC
- Storage Temperature : -55 ºC to +105 ºC
- Chassis & Terminal Finish : Electro Tin-Lead
- Chassis Material : 20 GA. Cold Rolled Steel
-
Control/Signal Line HEMP Filters High Performance
- Voltage Rating : 48 VDC or 120 VAC @ 0-60 Hz
- Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
- Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
- Insulation Resistance : Per MIL-PRF-15733, paragraph 4.6.7 with HEMP Protection Module removed.
- Dielectric Withstanding Voltage : Per MIL-PRF-15733, paragraph 4.6.5 with HEMP Protection Module removed.
- High Performance Insertion Loss: Per MIL-STD-220, 100 dB @ 14 kHz - 10 GHz
- Terminal Strength : Per MIL-PRF-15733, paragraph 4.6.11
- Voltage Discharge : Discharge to less than 30 Volts within 2 seconds after removal of power
- Terminals : 1/4" Quick Connect Tab
- Operating Temperature : -55 ºC to +71 ºC
- Storage Temperature : -55 ºC to +105 ºC
- Chassis & Terminal Finish : Electro Tin-Lead
- Chassis Material : 20 GA. Cold Rolled Steel
-
NEMA Cabinets for Multiple HEMP Filters
Signal Line NEMA Cabinets