CAD (0)
  • Cart is empty
  • Dimensional Drawing for Power Line HEMP Filters Standard Performance

    • Voltage Rating: 277/480 VAC @ 60 Hz
    • Current Rating: 5 through 150 amperes
    • HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
    • Insertion Loss: Standard performance (curve 1) per MIL-STD-220
    • Leakage Current: < 10% of rated current 10 through 150 amperes, < 1 amp for 5 amp filters
    • Insulation
    • more
  • Dimensional Drawing for Power Line HEMP Filters High Performance

    • Voltage Rating: 277/480 VAC @ 60 Hz
    • Current Rating: 5 through 150 amperes
    • HEMP Compliance: Per MIL-STD-188-125-1 and MIL-STD-188-125-2 as Power Line (Intrasite) point of entry filter for short (E1) and intermediate (E2) pulses.
    • Insertion Loss: high performance (curve 2) per MIL-STD-220
    • Leakage Current: < 10% of rated current 10 through 150 amperes, <1 amp for 5 amp filters
    • Insulation
    • more
  • HEMP/EMP Filters

    • Voltage : 0 to 480 Volts
    • Current : 0 to 100 Amps
    • Frequency : DC to 400 Hz
    • Insertion Loss : 100 dB minimum from 14 kHz to 10 GHz
    • Operating Temperature : -40 ºC to +71 ºC
    • Storage Temperature : -55 ºC to +105 ºC
    • Altitude : Maximum of 15,000 feet
    • Humidity : 10 to 90 Percent
    • Fungus : Non-nutritive materials are used
    • Corrosion : Hermetically sealed steel or aluminum enclosures with tin-lead plating

  • Control/Signal Line HEMP Filters Standard/High Performance

    • Voltage Rating : 48 VDC or 120 VAC @ 0-60 Hz
    • Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
    • Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
    • Insulation Resistance : Per MIL-PRF-15733, paragraph 4.6.7 with Hemp Protection Module removed.
    • Dielectric Withstanding Voltage : Per MIL-PRF-15733, paragraph 4.6.5 with Hemp Protection Module removed.
    • Standard Insertion Loss : Per MIL-STD-220, 20
    • more
  • Control/Signal Line HEMP Filters Standard/High Performance

    • Voltage Rating : 48 VDC or 120 VAC @ 0-60 Hz
    • Visual/Mechanical : Per MIL-PRF-15733, paragraph 4.6.1
    • Capacitance : Per MIL-STD-202, Method 305 @ 1 kHz
    • Insulation Resistance : Per MIL-PRF-15733, paragraph 4.6.7 with HEMP Protection Module removed.
    • Dielectric Withstanding Voltage : Per MIL-PRF-15733, paragraph 4.6.5 with HEMP Protection Module removed.
    • High Performance Insertion Loss: Per MIL-STD-22
    • more
  • NEMA Cabinets for Multiple HEMP Filters

    Signal Line NEMA Cabinets