CAD (0)
  • Cart is empty
100dB, 14KHz to 1 GHz measured per MIL-STD-220, 50ohms system 10 to 100% load current
Unit of Measure

Specifications

Brands

Captor

Alternating Current (AC) Voltage at 60 Hertz (Hz)

270 V480 V

Insulation Resistance

Per MIL-PRF-15733, prior to discharge resistor installation.

Dielectric Withstanding Voltage

2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to installation of discharge resistor

Voltage Drop

Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733

Voltage Discharge

Discharge to less than 30 Volts within 30s after removal of power

Operating Temperature

-40 to +65 ºC

Storage Temperature

-55 to +105 ºC

Insertion Loss

Measured per MIL-STD-220

Filter Type

High Performance Filter

Number of Lines

4

Current Rating

200 A

Estimated Weight

375 lb

Size

Size A

33.0 in

Size B

34.0 in

Size C

8.0 in

Size D

24.0 in

Size E

34.0 in

Enclosure

Enclosure

  • Modified: NEMA 1 type enclosure
  • Cabinet Material: Stainless Steel construction
  • Filter insert case material: Cold rolled steel construction with a corrosion resistant plating
  • Epoxy paint optional
  • Shielding effectiveness measured on clean side greater than 100 dB from 14 KHz or 100 KHz to 10 GHz
  • Dual removable access covers

Note

Note

When installed with best grounding practice, additional shielding and Isolation between input and output compartments
Specifications subject to change
Cabinet Supplied with Filter Inserts, 50 to 800 Amps 2, 3 and 4 Power Line filters Installed