100dB, 14KHz to 1 GHz measured per MIL-STD-220, 50ohms system 10 to 100% load current
Unit of Measure

Specifications

Brands

N/A Captor

Alternating Current (AC) Voltage at 60 Hertz (Hz)

N/A 270 V480 V

Insulation Resistance

N/A Per MIL-PRF-15733, prior to discharge resistor installation.

Dielectric Withstanding Voltage

N/A 2250 VDC line-to-chassis per MIL-STD-202, Method 301 prior to installation of discharge resistor

Voltage Drop

N/A Less than 1% of rated voltage per paragraph 4.6.8 of MIL-PRF-15733

Voltage Discharge

N/A Discharge to less than 30 Volts within 30s after removal of power

Operating Temperature

N/A -40 to +65 ºC

Storage Temperature

N/A -55 to +105 ºC

Insertion Loss

N/A Measured per MIL-STD-220

Filter Type

N/A High Performance Filter

Number of Lines

N/A 4

Current Rating

N/A 800 A

Estimated Weight

N/A 3700 lb

Size

Size A

N/A 2 x 50.0 in

Size B

N/A 60.0 in

Size C

N/A 12.0 in

Size D

N/A 40.0 in

Size E

N/A 2 x 52.0 in

Enclosure

Enclosure

N/A
  • Modified: NEMA 1 type enclosure
  • Cabinet Material: Stainless Steel construction
  • Filter insert case material: Cold rolled steel construction with a corrosion resistant plating
  • Epoxy paint optional
  • Shielding effectiveness measured on clean side greater than 100 dB from 14 KHz or 100 KHz to 10 GHz
  • Dual removable access covers

Note

Note

N/A Two A-11035-4 cabinets (two 400 A filter lines connected in parallel for each phase) for a total of four 800 A lines.
When installed with best grounding practice, additional shielding and Isolation between input and output compartments
Specifications subject to change
Cabinet Supplied with Filter Inserts, 50 to 800 Amps 2, 3 and 4 Power Line filters Installed